Semiconductor heating and cooling thermostat compressor fault detection instructions
In the semiconductor heating and cooling thermostat, the compressor is one of its core components. Once it fails, it will affect the operation of the whole system. How to solve the fault is better?
The faults of semiconductor heating and cooling thermostat compressors can be divided into motor faults and mechanical faults (including crankshafts, connecting rods, pistons, valve plates, cylinder head gaskets, etc.). Mechanical failure often causes the motor to overload or even stall, which is one of the main causes of motor damage.
The compressor motor load includes the load required to compress the gas and the load required to overcome the mechanical friction. If the pressure ratio is too large, or the pressure difference is too large, the compression process will be more difficult; the frictional resistance caused by the lubrication failure will increase, and the motor stall in extreme cases will greatly increase the motor load. Lubrication failure and increased frictional resistance are the primary causes of load anomalies.
The short circuit caused by the metal shavings of the compressor, the metal chips trapped in the windings are the main culprit for the short circuit and the low grounding insulation value. The normal vibration of the compressor during operation and the twisting of the winding by the electromagnetic force at each start-up will promote the relative motion and friction between the metal chips interposed between the windings and the winding enameled wire. Sharp edges and swarf can scratch the enameled wire insulation and cause a short circuit.
Compressor contactor problems, contactors can meet demanding conditions such as fast cycling, continuous overload and low voltage. They have a large enough area to dissipate the heat generated by the load current, and the choice of contact material prevents soldering at high currents such as startup or stall. In order to be safe and reliable, the compressor contactor must simultaneously disconnect the three-phase circuit. The method of disconnecting the two-phase circuit is not recommended.
The rated current of the compressor contactor must not be lower than the rated current on the compressor nameplate. Contactors with small specifications or poor quality cannot withstand compressor start-up, large current surges during stalling and low voltage, and are prone to single-phase or multi-phase contact jitter, soldering or even falling off, causing motor damage.
Semiconductor heating and cooling thermostat compressors may have more faults. It is not recommended for users to solve them themselves. It is recommended to contact the manufacturer for after-sales service.
Похожие рекомендации
-
Ultra-low temperature bearing cooling equipment Shrink Fit Bearings and Bushings and Pins
2153For the metallurgical industry, the oil pressure system of precision machine tools must use refrigeration to control the oil temperature to stabilize the oil film viscosity so that the machine tool can work normally. If applied to steel products, ...
Посмотреть детали -
Characteristics of Industrial Constant Temperature Recirculating Chiller
2202Points for attention in the use ofindustrial constant temperature recirculating chillerIndustrial constant temperature recirculatingchillers are widely used in pharmaceutical, chemical and laboratory. Next,let's introduce the characteristics...
Посмотреть детали -
What type of chiller is needed for low-temperature etching?
1416The low-temperature etching process usually requires extremely high precision temperature control and strong cooling ability to maintain stable operation of the etching equipment at extremely low temperatures, in order to achieve finer etchi...
Посмотреть детали -
What aspects need to be considered in the external circulation cooling system of the test bench?
1650As we all know, the test room needs to be equipped with a cooling system for vehicle performance and comprehensive transmission, road simulation, electromagnetic compatibility, power battery, vehicle environment and other tests. In the automobile...
Посмотреть детали
LNEYA Промышленные чиллеры Производитель Поставщик