Устранение распространенных неисправностей промышленного водяного охладителя
As we all know, with the rapid development of modern industrial technology, in order to improve production efficiency, improve product quality and reduce consumption costs, the demand for temperature control equipment in the process is higher and higher, but there are more and more product quality problems about some industrial water chillers, So we simply analyze some common problems about industrial water chillers.

Abnormal temperature at the inlet and outlet of cooling water: the water temperature at the inlet of condenser is too high (higher than 32 ℃), first check whether the fan of cooling tower can be reversed (there are such examples in practical engineering). Then, after technical demonstration and on the premise of feasibility, adjust the blade angle of the fan to improve the air volume of the fan.
Another phenomenon often occurs in the system with multiple cooling towers in parallel. When the local load is running, the temperature difference between the inlet and outlet of the condenser is too small. It is necessary to check whether each cooling tower has been equipped with an electric valve, or whether the set electric valve fails to form a cooling water bypass, which can not be cooled completely.
The differential pressure at the inlet and outlet of cooling water is abnormal. According to the relevant refrigeration theory, the heat release of the condenser will directly affect the refrigeration capacity. Therefore, the user should first check the cooling water system based on the pressure loss value on the main engine. If the pressure difference obtained from the value of the pressure gauge at the inlet and outlet greatly exceeds the normal value, it indicates that there are sundries at the inlet of the condenser.
Похожие рекомендации
-
Water cooled low-temperature circulators in the testing industry of new energy vehicles
1019The development of the new energy vehicle industry is relatively rapid. Driven by technological innovation, it is believed that the new energy vehicle industry is facing opportunities. However, with the development of the new energy vehicle indu...
Посмотреть детали -
Model and size selection of cooling and heating circulator (pilot plant temperature control system)
1084The cooling and heating circulator adopts mechanical refrigeration, the low-temperature heating tube heats the high temperature, and the canned pump is used as the circulating pump. The liquid circulation of the whole system is closed and consists...
Посмотреть детали -
Теплоноситель для систем охлаждения и нагрева в химической и фармацевтической промышленности
1125Система контроля температуры охлаждения и нагрева, также известная как циркулятор высокой и низкой температуры или система динамического контроля температуры, представляет собой оборудование для контроля температуры, используемое в фармацевтической и химической промышленности для обеспечения холода и ...
Посмотреть детали -
High-pressure failure of stainless steel cryogenic refrigerator
1292At the high speed of the stainless steel cryogenic refrigerator compressor, the temperature rises and the compressor generates high air pressure, which causes the high voltage protection relay to operate. The discharge pressure of the compressor r...
Посмотреть детали