Maintenance Method Of Ultra Low Temp Chiller Refrigeration System
Сайт ultra low temp chiller refers to the refrigeration unit whose chilled water temperature reaches below minus 35℃. The unit adopts two-stage compression refrigeration, and the combination of the scroll compressor and the piston compressor is used to manufacture a freezing source of minus 35℃ or even minus 60 ℃, to meet the requirements of the production process, to ensure the normal and smooth production.
Firstly, the leak detection of ultra low temp chiller system.
1. The refrigerant side of the unit has undergone a strict leak detection process during the factory and commissioning process.
2. After the unit is running, check the high-pressure part with the leak detector to ensure the tightness of all connections.
3. If a leak is found, it should be disposed of immediately. In general, the connection of the nano or flange bolts can be used to eliminate the leaks, but there is also the possibility that the refrigerant be recovered and then the leaks must be treated. Such as the leakage of welded joints.
Second, the system’s pressure leak detection.
The standard pressure leak detection steps for ultra low temp chillers are as follows:
1. Fill a small amount of R-22 gas to a system pressure of 2PSIG.
2. Fill the system with nitrogen to 25~50 PSIG. Make sure the pressure reaches all parts of the system. The oil valve can be opened slightly, and the leak detector is used to check whether there is refrigerant.
3. Check each joint and weld, and try to be careful and spend as much time as possible. The leak detection equipment used must be sensitive and reliable.
4. Open the top bleed valve of the evaporator and condenser to confirm that no refrigerant has been detected. If refrigerant is found, the end cap should be removed to remove the internal leak.
5. Confirm that the system is completely sealed, and the gas is released from the system at an appropriate flow rate from the filling valve to perform a certain purging action.
Thirdly, vacuuming and drying of ultra-low temperature chiller system.
1. Connect the high efficiency vacuum pump and the mercury vacuum gauge in series with the filling valve of the system.
2. Open all valves of the system that connect the valve, the suction valve and the vacuum gauge. Confirm that all valves that pass through the atmosphere are closed.
3. Start the vacuum pump and pump the vacuum to 5mmHg.
4. If there are conditions, 50oC of hot water can be introduced into the system to accelerate the evaporation of the system’s memory and improve the dryness.
Похожие рекомендации
-
Attention points for the use of rapid thermal cycle test airflow machine
1059The rapid thermal cycling test is a test equipment used in the metal, plastic, rubber, electronic and other material industries. It is used to test the material structure or composite material. It can be tolerated in a continuous environment of hi...
Посмотреть детали -
What are the factors that affect the price of industrial heating equipment in the industry?
918The price of heating and temperature control equipment is a part that many customers care about. The price is related to the brand, raw materials, and technology. At the same time, the technical parameter configuration of the product also has a gr...
Посмотреть детали -
How to maintain stable performance of biopharmaceutical laboratory oil cooler?
9131. A suitable working environment to prevent various failures of the oil cooler in the biopharmaceutical laboratory needs to provide a better operating environment for the equipment. Keep the environment clean and tidy, reduce the impact of vario...
Посмотреть детали -
What are the main hazards of the reaction kettle in the reactor intelligent temperature control syst
1161The intelligent temperature control system of the reactor is used in various chemical fines. With the constant attention of the industry safety issues, some risk factors of the intelligent temperature control system of the reactor should be avoide...
Посмотреть детали