Introduction To The Use Of Explosion-Proof Precision Chiller
Wuxi Lneya solves the problem of how to charge refrigerants in the absence of refrigeration.
1. Connect all kinds of equipment well, close the three valve when the vacuum pressure is down to 133.3Pa, remove the hose from the suction port of the vacuum pump, connect it on the R404 cylinder, and release the hose on the three valve.
2. Open the handle on the R404 cylinder slightly, and when the R404 refrigerant sprayed out of the loosened hose, the loosened hose was quickly fastened to the three valve (this is to remove the residual air in the hose).
3. Invert the R404 gas cylinder, the explosion proof precision chiller compressor is electrified, and the power line is put into the clamp type ammeter. Open the three-way valve handle so that the compressor can quickly shut down after inhaling part of the R404 refrigerant. Observe the pressure gauge pressure and the clamp ammeter, and the three valve handles are reopened after the pressure and current are reduced. After filling a part of the R12 refrigerant, the handle of the three valve is quickly closed, repeated so several times.
4. Through comprehensive observation: the pressure of the pressure gauge is stable at 0.03-0.05MPa (0.02-0.04MPa in winter and 0.05-0.07 MPa in summer). When the current of the clamp ammeter is steady at 0.6-0.8A, the condenser is evenly distributed and the filter temperature is slightly higher than the ambient temperature. The evaporator surface is evenly frosted and it will feel sticky. At this time, the amount of refrigerant charge is appropriate, that is, the capillary can be compressed by sealing pliers, then the capillary can be clipped by wire clamp and welded by oxygen welding at the fracture.
5. The soapy water is used to check the welding place.
Follow the steps and the refrigerant filling of the explosion-proof precision chiller should be completed basically, but it needs to be paid attention to that the refrigerant should not be overcharged at once in order to avoid failures.
Похожие рекомендации
-
Меры предосторожности для небольшого лабораторного охладителя воды до и после ввода в эксплуатацию
1966In the pharmaceutical and chemical industry, small laboratory water chillers are widely used refrigeration equipment, which are often used in various reaction kettles for refrigeration reactions. In order to maintain the stable operation of the e...
Посмотреть детали -
Заняла второе место в 2022 году
244718 ноября 2022 года при поддержке Ассоциации науки и техники провинции Цзянсу, Управления по делам Тайваня, Департамента промышленности и информационных технологий провинции, Департамента сельского хозяйства провинции...
Посмотреть детали -
-
Instructions for using the hydrogenation reactor cooling and heating integrated system
1897There are many accessories in the hydrogenation reactor cooling and heating integrated system, from the compressor to the electrical components. LNEYA reminds you that if you find more evaporator freezing oil, it is recommended to deal with it in ...
Посмотреть детали
LNEYA Промышленные чиллеры Производитель Поставщик