Как предотвратить слишком низкое давление замерзания в ящике для быстрого замораживания подшипников?
In the refrigeration system of the bearing blast chiller, if the condenser installation is not in the enclosed space, the system’s exhaust pressure (condensation pressure) tends to be lower in winter (or low temperature), which is often more common in the north. For bearing blasters, this is also the case for other equipment.
The low condensing pressure of the bearing quick freezing box will make the expansion valve unable to obtain sufficient pressure drop at both ends, and it is difficult to supply the appropriate refrigerant to the evaporator. On the one hand, the cooling capacity of the refrigeration system will not meet the requirements, and the system will also be made. Frequent low-voltage alarms and other faults.
To this end, we can deal with the method of exhaust pressure controller. When the intermittent operation of the fan is simple and easy to use, and the technology is mature, the controller used is a pressure controller. This pressure controller can control the intermittent start and stop of the fan. When the pressure is too low, turn off the fan. When the pressure is too high, turn on the fan. Generally, on a small-capacity unit, use two or more fans, one of which is normally open, and the other fans are pressure controlled. The controller controls the start or stop of the fan by the level of the condensing pressure.
It is also possible to use a pneumatic control device to utilize a high-pressure refrigerant-driven piston-type damper. This control device can operate as a stable exhaust pressure as the fan speed controller; the main reason is that the inlet pressure of the expansion valve does not resemble a fan. Intermittent operation produces large fluctuations, and the louver device can be installed either at the air inlet or at the air outlet.
In addition, the condenser overflow device can also be used to increase the condensing pressure of the system by using excess refrigerant, and the condenser overflow device is used for warming or low temperature environment, and the large flow refrigerant is taken from the liquid storage device. It is sent to the condenser, and the excess refrigerant is used to increase the condensing pressure of the system, thereby avoiding the failure of the condensing pressure being too low at low temperatures.
LNEYA’s methods to prevent the bearing chiller from condensing too low pressure are still relatively high, and users can try it according to their own needs.

Похожие рекомендации
-
На что следует обратить внимание в системе охлаждения реакционного чайника с азотной кислотой?
973Приобретая систему охлаждения реактора азотной кислотой, многие пользователи часто не замечают деталей, на которые необходимо обратить внимание при включении оборудования. Необходимо проверить, не мало ли частей изделия, которые...
Посмотреть детали -
Principle analysis of operation of refrigeration heating circulator
1156With the continuous development of technology, more and more refrigeration equipment has appeared in our lives, such as: refrigeration and heating circulators, in fact, they are not ordinary, are remarkable refrigeration equipment. The refrigerati...
Посмотреть детали -
Meet at booth 6002 of Shanghai World Expo Hall【Testing Expo】9.14-9.16
928Exhibition name: Shanghai International Automobile Testing and Quality Control ExhibitionExhibition time: September 14-16, 2020Booth number: 6002Exhibition address: Shanghai World Expo Exhibition Hall, Hall 1,
Посмотреть детали -
What if the cooling rate of the cooling and heating temperature control system of the reactor slows
1077LNEYA cooling and heating temperature control system is a laboratory instrument and equipment for temperature control of supporting reactors in pharmaceutical and chemical laboratories and other industries. It adopts a fully closed circulation pip...
Посмотреть детали